Troubleshooting checklist CD-30
22
11 Troubleshooting checklist
Caution!
This device may only be repaired by specialist personnel.
Inadequate repairs can lead to considerable hazards.
Compressor does not run
Key
U
KL
: Voltage between the positive and negative electronic terminals
U
ON
: Switch on voltage of the electronic connection terminals
(see “Technical description” chapter on page 17)
U
OFF
: Switch off voltage of the electronic connection terminals
(see “Technical description” chapter on page 17)
Interior temperature too low in the “MIN” thermostat setting
Feature Possible cause
U
KL
= 0 Volt Connection supply line interrupted
Battery/main electronic switch defective (if installed)
Additional supply line fuse has blown (if installed)
U
KL
U
ON
Battery voltage is too low
During attempted start up
U
KL
U
OFF
Loose cable connection/poor contact (corrosion)
Cable cross section too small
Battery capacity too low
During attempted start up
U
KL
U
ON
.
Ambient temperature too high
Insufficient ventilation
Condensor is dirty
Fan defective (if installed)
Electric circuit between
the pins in the compressor
interrupted
Defective compressor
Feature Possible cause Remedy
Compressor runs
continuously
Thermostat sensor has no contact to the
vaporiser
Secure the sensor
Short circuit in the thermostat line Change the thermostat
Thermostat defective
Compressor runs for a
long time
Large quantities have been frozen in the
vaporiser compartment
CD-30.book Seite 22 Freitag, 1. April 2005 4:47 16